GCS Series Low‑Voltage Draw‑out Switchgear

Product Overview:

Suitable for power plants, substations, petrochemical, industrial plants, high‑rise buildings – for power distribution, motor control, and capacitor compensation. High breaking capacity and dynamic/thermal stability, complies with IEC 60439‑1, GB 7251, JB/T 9661.

Operating Conditions: (same as GCK):

1. Ambient temperature –5℃~+40℃, 24h average ≤35℃
2. Relative humidity: ≤50% at 40℃, ≤90% at 20℃
3. Altitude <2000m
4. Storage/transport: –25℃~+55℃ (short‑term up to +70℃)


Features:
1. Functional compartments strictly separated, each unit independent
2. Horizontal busbars arranged at rear, strong short‑circuit electromagnetic withstand
3. Multiple drawer sizes; up to 22×1/2 units per cabinet
4. Drawer positions: connect, test, disconnect, withdraw, isolate
5. Mechanical interlocking and emergency release for safety


Key Technical Parameters:
1.Rated frequency: 50Hz
2.Rated voltage: 400/380V
3.Rated insulation voltage: 690V
4.Horizontal busbar current: ≤6300A
5.Vertical busbar current: ≤4000A
6.Horizontal busbar short‑time withstand: 100kA
7.Vertical busbar short‑time withstand: 65kA
8.Protection: IP40, IP30


Additional Information:

Computer interface available for online monitoring; contact us for details. (Custom‑made to drawings,Production cycle of  15‑30 days)

Reviews

There are no reviews yet.

Be the first to review “GCS Series Low‑Voltage Draw‑out Switchgear”

Your email address will not be published. Required fields are marked *