MNS Series Low‑Voltage Draw‑out Switchgear

Product Overview:

Advanced low‑voltage draw‑out switchgear, adaptable to various power supply and distribution scenarios. Widely used in power plants, substations, industrial plants, municipal projects, etc. Complies with GB 7251.12, JB/T 9661, IEC 439‑1.

Operating Conditions: (same as GCK):

1. Ambient temperature –5℃~+40℃, 24h average ≤35℃
2. Relative humidity: ≤50% at 40℃, ≤90% at 20℃
3. Altitude <2000m
4. Storage/transport: –25℃~+55℃ (short‑term up to +70℃)


Features:
1. Compact design, more functional units in smaller space
2. 25mm modular components, flexible and versatile assembly
3. Flame‑retardant barrier boards protect busbars, safe operation
4. Drawer positions: connect, test, disconnect
5. High‑strength flame‑retardant engineering plastics, superior protection


Key Technical Parameters:
1.Rated frequency: 50Hz
2.Rated voltage: 400/380V
3.Rated insulation voltage: 690V
4.Horizontal busbar current: ≥6300A
5.Vertical busbar current: ≤1250A
6.Horizontal busbar short‑time withstand: 80kA
7.Protection: IP40, IP30


Additional Information:

Computer interface available for online monitoring; contact us for details. (Custom‑made to drawings, Production cycle of  15‑30 days)